Parameter |
PKZ-АR-0,1 |
PKZ-АR-0,3 |
PKZ-АR-0,6 |
PKZ-АR-1 |
PKZ-АR-2 |
PKZ-АR-3 |
PKZ-АR-4 |
PKZ-АR-5 |
Operating range of network voltage, V |
164 — 255 |
Nominal output energy power, kW |
0.1 |
0.3 |
0.6 |
1 |
2 |
3 |
4 |
5 |
Range of output power operating values, kW |
0.02-0.1 |
0.02-0.3 |
0.03-0.6 |
0.03-1.0 |
0.06-2.0 |
0.09-3.0 |
0.12-4.0 |
0.15-5.0 |
Complete watt consumption, max kVa |
0.13 |
0.4 |
0.74 |
1.24 |
2.47 |
3.70 |
4.94 |
6.17 |
Efficiency coefficient at output power, equal 1.0 Рnom |
0.90 |
Efficiency coefficient at output power, equal 0.5 Рnom |
0.84 |
Efficiency coefficient at output power, equal 0.2 Рnom |
0.75 |
Power coefficient |
0.9 |
Power coefficient |
48 |
48/96 |
Nominal output current, А |
2 |
6 |
12 |
20/10 |
40/20 |
60/30 |
80/40 |
100/50 |
Range of operating values for total output current of output voltage range "0-48V", A |
0.2-2 |
0.3-6 |
0.6-12 |
1-20 |
2-40 |
3-60 |
4-80 |
5-100 |
Range of operating values for total output current of output voltage range "0-96V", A |
— |
0.5-10 |
1.0-20 |
1.5-30 |
2.0-40 |
2.5-50 |
Coefficient of output voltage (current) pulses , %, max |
1.0 |
Range of output current threshold, %, min |
5-100 |
Range of total potential threshold, V |
from −0.8 to −3.5 |
Range of polarized potential threshold, V |
from −0.8 to -2.0 |
Accuracy of total potential maintenance, % |
1.0 |
Accuracy of polarized potential maintenance, % |
1.0 |
Accuracy of output (protective) current maintenance, % |
1.0 |
Input resistance of measurement unit of protective potential at normal climate conditions, MОm, min |
10 |
Dimensions, mm |
450×600×800 |
Weight PKZ-АR with a cabinet, kg |
52 |
52 |
52 |
52 |
57 |
62 |
86 |
91 |
Warranty service life, years |
3 |
Life cycle, years |
25 |